FLA 90

Sunlee controls offers the most complete line of Definite Purpose (DP) contactors in the industry. Designed for heating, ventilation, air conditioning and refrigeration (HVACR) applications, SunLee’s DP contactors are designed to handle the most challenging installations.

FLA:90

Poles:3

Resistive Amps:120

Coil Voltage:24/120/240/480 VAC

Hertz:50/60

Locked Rotor Amps 240/480/600:540/450/360


DESCRIPTION

Nomenclature

FLA

Poles

24 V Coil

120V Coil

208/240V Coil

277V Coil

480V Coil

90

FLA

3

DRC-3XQ09CJ

DRC-3XT09CJ

DRC-3XU09CJ

DRC-3XV09CJ

DRC-3XH09CJ

 

Features

· UL 508/UL 60947-1 File NO. E508253

· Snap-on auxiliary contacts

· Quick-connect terminals

· Silver Cadmium Oxide Contacts

· Coils have class F insulation

· Includes Lug, spade terminals, and covers.

· Base assembly is made from high performance Bulk (Dough) molding compounds

Initial Dielectric Strength

Between Contacts & Coils: 2,200 VAC
Between Poles: 2,200 VAC (includes shunt)
Between Open Contacts: 2,200 VAC (no shunt)

Insulation System

155°C Class F

Temperature Range

-40°C to +65°C
-40°F to +150°F

Power Pole Terminations

Aluminum box lug

Wire Size

75/90 FLA Box Lug   14-1

Recommended Tightening Torque

Box lug: 50 in. lbs

Quick Connects

Coil terminals:
Dual: .250″ QC or #6–32 screw/.250″ QC

Power terminals:

Dual .250″ QC